Wyreless Access
print icon

Overview

This document outlines how to install and configure the WAG-PIM-485-16TD.

Prerequisites

The following is a brief description of what is needed before attempting to make the WAG-PIM-485-16TD work with Access It! Universal.

Wireless Access Gateway (WAG)

The WAG looks just like a MINI-SCP except the firmware has been changed allowing for communications between the SCP and the PIM-485-16TD.

  • Firmware Label Markings:
    • 10288 6 SCP-CPI
    • U4 R1.03
    • MSC (c)03 PIM

Panel Interface Module (PIM-485-16TD)

The PIM-485-16TD communicates to the WAG via 2 wire RS-485 and wirelessly communicates with field hardware known as WAs. WAs are battery powered and can be configured with proximity or magstripe readers. The WAs are mounted directly to the door and control both lockset and request to exit. A total of 16 WAs can be attached to one PIM-485-16TD.

The PIM-485-16TD must first be linked to the WAs which may be accomplished by using the manufacturer's Configuration & Demonstration Tool (CDT).

Refer to the manufacturer’s documentation to perform this procedure.

Hardware Settings

WAG Jumper Settings

J3 485   J9 485
J4 485   J10 Closed
J5 485   J11 Opened
J6 485   J12 Closed
J7 2W   J13 Closed
J8 Closed      
.  

PIM-485-16TD Jumper Settings

J6 Closed   J9 Closed
J8 Closed   J10 Closed
.  

Wiring WAG To PIM-485-16TD

The WAG is wired to the PIM-485-16TD using standard 2 wire RS-485.

WAG PIM-485-16TD
TR2+ TA- & RA-
TR2- TB+ & RB+
GND  GND
.  

Wiring WAG To SCP

The WAG is wired to the SCP as a standard SIO.

WAG SCP
TR1+ TR2+
TR1- TR2-
GND GND
.  

Software Settings

Enable WAG

  1. From the file menu, click Go | Main | Hardware
  2. Edit the SIO to be enabled as a WAG from the right hand pane
  3. Select GW-RecognitionSource from the Model drop list
  4. Check the Device Installed check box
  5. Set the Comm Channel (IN) by selecting the appropriate number from the drop list
  6. Set the Comm Channel (OUT) by selecting the appropriate number from the drop list
  7. Select the Options tab
  8. Set the Number of Readers the WAG will control by clicking the up and down arrows
  9. Click the Save button

Configure GW-RecognitionSource Readers

  1. Edit the one of the newly created GW-RecognitionSource readers
  2. Select the Readers Settings tab
  3. Select Wyreless Access from the Reader Type drop list
    If the Wyreless Access reader type is not available from the Reader Type drop list, see the Add Wyreless Access Reader Type section within this document.
  4. Click the Save button
  5. Repeat steps 1 through 4 for all of the newly created GW-RecognitionSource readers

Add Wyreless Access Reader Type

  1. Edit the one of the newly created GW-RecognitionSource readers
  2. Select the Readers Settings tab
  3. Click the Edit… button to add the Wyreless Access reader type
  4. Click the New button from within the Edit Reader Types window
  5. Enter Wyreless Access into the Reader Type Name field
  6. Select the Keypad Mode tab
  7. Select the MR-20 8-bit format, with tamper support radio button
  8. Click the OK button
  9. Click the Save button
    The Wyreless Access reader type will now be available from the Reader Type drop list.
  10. Return to the Configure GW-RecognitionSource Readers section within this document